Transformer Turn Ratio Tester TTR Tester
Basic Info
Model NO. | XHBB128A |
After-sales Service | Warranty Certificate |
Warranty | Warranty Certificate |
Usage | Network Cable Tester, HDMI Cable Tester, Audio Cable Tester, Coaxial Cable Tester, Digital Cable Tester |
Certification | CE |
Customized | Customized |
Trademark | XZH TEST |
Origin | China Xi′an |
HS Code | 854320100 |
Production Capacity | 1000 Pieces /Year |
Packaging & Delivery
Package size per unit product 35.00cm * 24.00cm * 18.00cm Gross weight per unit product 30.000kgProduct Description
XHBB128ATransformation ratio tester
Description
During the production process of semi-finished products and finished products of power
transformers, before the newly installed transformers are put into operation and in accordance with
the preventive test procedures of the National Electric Power Ministry, it is required that the
transformers in operation be regularly tested for the turns ratio or voltage ratio. The traditional
variable bridge operation is cumbersome, the reading is not intuitive, and the necessary conversion
is performed. The test result is only a phase change ratio. The automatic ratio change tester
overcomes the shortcomings of the traditional turn ratio test. The instrument completes the
three-phase ratio test at a time, and the test speed is fast and the accuracy is high.
Features:
1). The test range is wide, up to 5000.
2).Test speed is fast, 7 seconds to complete the three-phase test
3) .Z-connected transformer test.
4). The clock and date display even power is off, data storage.
5). High and low voltage reverse connection protection function.
6). Transformer short circuit, inter-turn short circuit protection.
7). Thermal printer output function, fast, silent.
8). Equipped with RS232, USB interface, easy to connect to the computer to export data.
9). Small size and light weight.
Technical data
1). Range: 0.9 ~ 5000
2). Accuracy: 0.1% (<500)
0.2% 2 words (500~2000)
0.5% word (2000 or more)
3). Resolution: minimum 0.0001
4). Output voltage: 160V, 10V automatic shift
5). Working power: AC220V±10% 50HZ
6). Working temperature: -20 °C ~ 40 °C
7). Relative humidity: ≤ 85%, no condensation