banner
Products
Quality and performance are the hallmarks of our products.
Dissolved Gas in Oil Chromatorgraphy Tester

Dissolved Gas in Oil Chromatorgraphy Tester

Dissolved Gas in Oil Chromatorgraphy Tester I. Application Suitable for the determination of the content of dissolved ga;
Basic Info
Model NO. hm9890
Customized Customized
Structure Portable
Material Steel
Certification ISO
Application Lab
Type Measurement Type
Baseline Noise ≤2 *10-13A
Linear >106
Sensitivity >5000mv Ml / Mg
Baseline Drift ≤100μV / 30min
Product Name Transformer Oil Dissolved Gas Analyzer
Transport Package Wooden Box with Foam Inside
Trademark HMDQ
Origin Hubei, China(Mainland)
Production Capacity 100sets Per Year
Product Description
Dissolved Gas in Oil Chromatorgraphy Tester

I. Application

Suitable for the determination of the content of dissolved gas components in insulating oil of electric power system. It can complete 7 kinds of gas components H2, CO, CO2, CH4, C2H4, C2H6, C2H2 (hydrogen, carbon monoxide, carbon dioxide) dissolved in insulating oil at one injection. Full analysis of the content of methane, ethylene, ethane, acetylene, and the minimum detectable concentration of acetylene was 0.06 ppm.

II.Specification :
The detection limit: ≤2 × 10-12g / s (n-hexadecane / iso-octane)
Baseline Noise: ≤2 × 10-13A
Baseline Drift: ≤2 × 10-12A / 30min
Linear: ≥106
Adjustable automatic ignition
Settling time: ten minutes
the thermal conductivity detector (TCD):
Semi-diffused structure
Power supply with constant current control mode
Sensitivity: ≥5000mV · ml / mg.
Baseline noise: ≤10μV.
Baseline Drift: ≤100μV / 30min.
Linear ≥ 105
large-screen LCD display:
Clearly show the temperature set point and the brightest, the measured
values and the protection value
Real-time status display instrument
Automatic ignition
temperature indicators:
Oven: the temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
Injector: The room temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
Detector: the temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
Reformer: The room temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
the other parameters:
Power: 220V ± 22V, 50Hz,
Power: ≥2 kW

More detailed pictures for transformer oil gas dissolved gas analyzer as below :

Dissolved Gas in Oil Chromatorgraphy Tester


Dissolved Gas in Oil Chromatorgraphy Tester


Dissolved Gas in Oil Chromatorgraphy Tester

Dissolved Gas in Oil Chromatorgraphy Tester

Dissolved Gas in Oil Chromatorgraphy Tester


Send inquiry